Parameter Range Default Description
From Monitoring On
Always
Activation
Delay
ACTIVATION
1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
Circuit Fault
Action
CKT
None
Notification
Warning
Electrical Trip
Shutdown
None Configure the action for an open circuit failure.
Lube Oil
Pressure Sensor
Calibration
Resistance: 10 to 100
Ω
Pressure: 1.0 to 10.0
bar
-
Configure the resistance and pressure values
for the 10 measurement points in the calibration
table.
Analogue Input 4 (LOP/DIG I)
Parameter
Range Default Description
Use Input As
Not used
Digital Input I
S4 Sensor mA
Not used Select what to use the input as.
Source
See Digital input
source selection in
this document
Not used Select the source from the list.
Name
Auxiliary Input I - You can configure the name of the input.
Polarity
Close to Activate
Open to Activate
Close to Activate Select the polarity for the input.
Action
None
Notification
Warning
Electrical Trip
Shutdown
None Select the action when the input is activated.
Activation
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
Configure from when the digital input is
monitored.
Activation
Delay
ACTIVATION
1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
Circuit Fault
Action
CKT
None
Notification
Warning
Electrical Trip
Shutdown
None Configure the action for an open circuit failure.
Lube Oil
Pressure Sensor
Calibration
Current: 4 to 20 mA
Pressure: 0.0 to 10.0
bar
-
Configure the current and pressure values for
the 10 measurement points in the calibration
table.
User manual 4189341340A EN Page 25 of 76