Parameter Range Default Description


 Low Fuel Level
Warning

Enable
Disable
Enabled
If this parameter is enabled, the controller
shows a notification when the fuel level is less
than the notification set point 

 Warning
Threshold


2 to 80 % 12 %
The controller shows a notification when the
fuel level is less than this set point.
 Fuel Tank
Capacity
 TANK 
2 to 1000 litre 100 litre Configure the fuel tank capacity.
 Fuel Theft
Warning
 THEFT 
Enable
Disable
Enabled
If this parameter is enabled, the controller
activates an alarm when the fuel level is less
than the set point for the fuel theft alarm.
 Fuel Theft Alarm
Threshold
 LVL 
1 to 100 % per hour 50 %
If the fuel consumption per hour is more than
this set point, the controller activates an alarm.
The percentage is of the nominal fuel
consumption.
 Circuit Fault
Action
 CKT 
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when there is an open
circuit failure.
 Fuel Sensor
Reference
 LVL 
Battery Negative
Engine Body
Engine Body Select the reference point for the fuel sensor.
 Fuel Level
Sensor Calibration
Table
Resistance: 0 to 1000
Ω
Fuel level: 0 to 100 %
-
Configure the resistance and fuel level values
for the 10 measurement points in the calibration
table.
Analogue Input 3 (LOP / DIG F)
Parameter
Range Default Description
Use Input As
 
Not used
Digital Input F
Lube Oil Pressure
Not used Select what to use the input as.
 Source
 
See Digital input
source selection in
this document
Not used Select the source from the list.
Name

Auxiliary Input F - You can configure the name of the input.
 Polarity
 
Close to Activate
Open to Activate
Close to Activate Select the polarity for the input.
 Action
 
None
Notification
Warning
Electrical Trip
Shutdown
None Select the action when the input is activated.
 Activation
 
Never
From Engine Start
From Monitoring On
Configure from when the digital input is
monitored.
User manual 4189341340A EN Page 24 of 76