Parameter Range Default Description
Start Time
to hour hours Configure the start time for the sequences.
Duration
ON
00 hr 01 min. to 99 hr
59 min.
10 hours, 10 minutes
Configure for how long the genset operates
during the scheduled sequences.
Load Transfer
Enable
Disable
Not enabled
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
3.5.2 Digital inputs
Digital Input # (DIG IN #)
Parameter
Range Default Description
Source
See Digital input
source selection in
this document
- Select an input source from the list.
Name
Auxiliary Input # - You can configure the name of the input.
Polarity
Close to Activate
Open to Activate
Close to Activate
You can select how to activate the input. It can
be open or close with reference to ground.
Action
None
Notification
Warning
Electrical Trip
Shutdown
None
You can configure what action occurs when the
digital input is activated.
Activation
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
You can configure when the controller starts to
monitor the digital input.
Activation Delay
0 to 60 s 1 s
When the timer expires, the configured action
occurs.
3.5.3 Analogue inputs
Analogue Input 1 (ENG TEMP / DIG G)
Parameter
Range Default Description
Use Input As
Not used
Digital Input G
Engine Coolant
Temperature Sensor
Not used Select the input.
Source
See Digital input
source selection in
this document
Not used Select the source from the list.
Name
Auxiliary Input G - You can configure the name of the input.
Polarity
Close to Activate
Open to Activate
Close to Activate Select the polarity for the input.
Action
None
Notification
None Select the action when the input is activated.
User manual 4189341340A EN Page 22 of 76