Communication (RS485 COMM)
Level 2 Range Default Description
Communication Mode
 
None
Modbus
None Select the communication mode.
Server ID
 SLAVE 
1 to 247 2 Select the server ID for Modbus.
Baud rate

1200
2400
4800
9600
19200
38400
57600
115200
9600 bps
Select the baud rate for the serial
communication.
Parity Bit

None
Even
Odd
None
Select the parity bit for the serial
communication.
Auto Exercise – Event 1 (AUTO EXERCISE – 1)
Level 2
Range Default Description
Auto Exercise
 
Enable
Disable
Not enabled
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Event Occurrence
 
Daily
Weekly
Monthly
Daily Configure how often the sequences occur.
Event Day
 
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
Runs every day Configure the start date for the sequences.
Start Time
 
 to  hour  hour Configure the start time for the sequences.
Duration
 ON 
00 hr 01 min. to 99 hr
59 min.
10 hours, 10 minutes
Configure for how long the genset operates
during the scheduled sequences.
Load Transfer
 
Enable
Disable
Not enabled
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Auto Exercise – Event 2 (AUTO EXERCISE – 2)
Parameter
Range Default Description
Auto Exercise
 
Enable
Disable
Not enabled
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Event Occurrence
 
Daily
Weekly
Monthly
Daily Configure how often the sequences occur.
Event Day
 
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
Runs every day Configure the start date for the sequences.
User manual 4189341340A EN Page 21 of 76