Parameter Range Default Description
Warning
Electrical Trip
Shutdown
 Activation
 
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
Configure from when the digital input is
monitored.
 Activation
Delay
 ACTIVATION

1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
 Circuit Fault
Action
 CKT 
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when there is a circuit
failure.
 Engine
Temperature Sensor
Calibration Table
Resistance: 0 to 1000
Ω
Temperature: 25 to
300 °C
-
Configure the resistance and temperature
values for 10 measurement points in the
calibration table.
Analogue Input 2 (FUEL LVL / DIG H)
Parameter
Range Default Description
Use Input As
 
Not used
Digital Input H
Fuel Level Sensor
Not used Select what to use the input as.
 Source
 
See Digital input
source selection in
this document
Not used Select the source from the list.
Name

Auxiliary Input H - You can configure the name of the input.
 Polarity
 
Close to Activate
Open to Activate
Close to Activate Select the polarity for the input.
 Action
 
None
Notification
Warning
Electrical Trip
Shutdown
None Select the action when the input is activated.
 Activation
 
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
Configure from when the digital input is
monitored.
 Activation
Delay
 ACTIVATION

1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
 Low Fuel Level
Shutdown

Enable
Disable
Not enabled
If this parameter is enabled, the controller shuts
down the engine when the fuel level is less than
the shutdown set point 

 Shutdown
Threshold
0 to 78 % 10 %
The controller shuts down the engine when the
fuel level is less than this set point.
User manual 4189341340A EN Page 23 of 76