Parameter Range Default Description
Warning
Electrical Trip
Shutdown
Activation
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
Configure from when the digital input is
monitored.
Activation
Delay
ACTIVATION
1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
Circuit Fault
Action
CKT
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when there is a circuit
failure.
Engine
Temperature Sensor
Calibration Table
Resistance: 0 to 1000
Ω
Temperature: 25 to
300 °C
-
Configure the resistance and temperature
values for 10 measurement points in the
calibration table.
Analogue Input 2 (FUEL LVL / DIG H)
Parameter
Range Default Description
Use Input As
Not used
Digital Input H
Fuel Level Sensor
Not used Select what to use the input as.
Source
See Digital input
source selection in
this document
Not used Select the source from the list.
Name
Auxiliary Input H - You can configure the name of the input.
Polarity
Close to Activate
Open to Activate
Close to Activate Select the polarity for the input.
Action
None
Notification
Warning
Electrical Trip
Shutdown
None Select the action when the input is activated.
Activation
Never
From Engine Start
From Monitoring On
Always
From Monitoring On
Configure from when the digital input is
monitored.
Activation
Delay
ACTIVATION
1 to 60 s 1 s
If the input is active when the timer expires, the
controller actives the action for the digital input.
Low Fuel Level
Shutdown
Enable
Disable
Not enabled
If this parameter is enabled, the controller shuts
down the engine when the fuel level is less than
the shutdown set point
Shutdown
Threshold
0 to 78 % 10 %
The controller shuts down the engine when the
fuel level is less than this set point.
User manual 4189341340A EN Page 23 of 76