Parameter Range Default Description
CURR
Over-current Delay
CURR
1 to 600 s 1 s
When the delay timer expires, the action for
over-current is activated if the current is more
than over-current set point.
CT Location
On Alt Output Cable
On Load Cable
On Alt Output Cable
Configure the location of the CT. You can place
the CT on the line from the genset or on the
load cable.
Load Monitoring (LOAD MONITOR)
Parameter
Range Default Description
Overload Action
None
Notification
Warning
Electrical Trip
Shutdown
None
The action that occurs when the load is more
than the overload set point.
Overload Threshold
50 to 150 % 90 %
The action for overload is activated when the
load is more than this set point.
Overload Monitoring
Delay
MON
1 to 600 s 1 s
When the delay timer expires, the action for
overload is activated if the load is more than
the overload set point.
Unbalanced Load
Action
LOAD
None
Warning
Electrical Trip
Shutdown
Notification
None
The action that occurs when the load is more
than the unbalanced load set point.
Unbalanced Load
Threshold
LOAD
5 to 200 % 5 %
The action for unbalanced load is activated
when the load is more than this set point.
Unbalanced Load
Delay
LOAD
1 to 600 s 1 s
When the delay timer expires, the action for
unbalanced load is activated if the load is more
than the unbalanced set point.
Low Load Enable
Enable
Disable
Not enabled
If this parameter is enabled, the configured
action for low load is activated.
Low Load Action
None
Warning
Electrical Trip
Shutdown
Notification
None
The action that occurs when low load is
detected. Low load is detected when the load is
less than the set point for low load trip
LOAD
Low Load Trip 1 to 99 % 50 %
The set point for low load. When the load is less
than this set point, the action for low load is
activated.
Low Load Return 2 to 100 % 51 %
If the action for low load is a warning, the
controller stops monitoring low load when the
load is more than this set point.
Low Load Delay 1 to 3600 s 1 s
If the load is less than the set point for low load
when the time expires, the low load action is
activated.
User manual 4189341340A EN Page 31 of 76