Parameter Range Default Description
Under-frequency
Shutdown Delay
SHUTDOWN
0.1 to 100 s 10 s
If the frequency is less than the set point for
under-frequency shutdown SHUTDOWN
when this timer expires, the controller
shuts down the engine.
Under-frequency
Warning Enable
FREQ
Enable
Disable
Not enabled
If this parameter is enabled, the display shows
a warning when the voltage is less than the set
point for the under-voltage warning.
Under-frequency
Warning Threshold
WARNING
11.0 to 60.0 Hz 90 Hz
When the frequency is less than this set point,
the controller shows a warning message.
Under-frequency
Warning Delay
WARNING
0.1 to 100 s 10 s
If the frequency is less than the set point for
under-frequency warning WARNING
when this timer expires, the controller
activates a warning alarm.
Over-frequency
Shutdown Enable
FREQ
Enable
Disable
Not enabled
If this parameter is enabled, the controller shuts
down the engine when the frequency is more
than the configured set point for over-
frequency.
Over-frequency
Shutdown Threshold
SHUTDOWN
26.0 to 75.0 Hz 120 Hz
When the frequency is more than this set point,
the engine shuts down.
Over-frequency
Shutdown Delay
SHUTDOWN
0.1 to 100 s 10 s
If the frequency is more than the set point for
over-frequency shutdown SHUTDOWN
when this timer expires, the controller
shuts down the engine.
Over-frequency
Warning Enable
FREQ
Enable
Disable
Not enabled
If this parameter is enabled, the controller
shows a warning message when the frequency
is more than the set point for the over-
frequency warning.
Over-frequency
Warning Threshold
WARNING
25.0 to 74.0 Hz 110 Hz
When the frequency is more than this set point,
the controller activates a warning alarm.
Over-frequency
Warning Delay
WARNING
0.1 to 100 s 10 s
If the frequency is more than the set point for
over-frequency warning WARNING
when this timer expires, the controller
shuts down the engine.
Current Monitoring (CURRENT MONITOR)
Parameter
Range Default Description
CT Ratio
CT
0 to 8000 / 5 150/5 CT ratio.
Over-current Action
CURR
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when over-current is
detected.
Over-current
Threshold
5 to 10000 A 120
The action for over-current is activated when
the current is more than this set point.
User manual 4189341340A EN Page 30 of 76