Parameter Range Default Description
Idle to Rated Delay
Time
0 to 1200 s 10 s
Time for the engine to go from idle speed to
rated speed.
Start-up Idle Mode
Time
0 to 1200 s 10 s
The engine operates at low speed for this time
duration. You can configure the low speed with
the Initial Low Speed parameter.
Stopping Idle Time 0 to 1200 s 10 s
In idle mode, the engine operates at low speed
for this time duration before the engine shuts
down.
Idle Mode Pulse Time 0 to 60 s 2 s The pulse time for the idle mode output.
Battery Monitoring (BATTERY MONITOR)
Parameter
Range Default Description
Low Battery Voltage
Action
VOLT
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when the battery
voltage is low.
Low Battery Voltage
Threshold
VOLT
8.0 to 31.0 V 8.0 V
The action for low battery voltage is activated
when the voltage load is less than this set
point.
Low Battery Voltage
Delay
VOLT
5 to 1800 s 30 s
If the battery voltage is less than the low
voltage set point VOLT
when the timer expires, the controller activates
the action for low battery voltage.
High Battery Voltage
Action
VOLT
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for when the battery
voltage is high.
High Battery Voltage
Threshold
VOLT
9.0 to 32.0 V 15 V
The action for high battery voltage is activated
when the voltage load is more than this set
point.
High Battery Voltage
Delay
VOLT
5 to 1800 s 30 s
If the battery voltage is more than the set point
for high voltage VOLT
when the timer expires, the controller activates
the action for high battery voltage.
Charging Alternator Monitoring (CHARGE ALT MON)
Parameter
Range Default Description
Charging Alternator
Fail Action
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for charging alternator
failure.
Charging Alternator
Fail Threshold
0.0 to 35.0 V 10.0 V
The action for charging alternator failure is
activated when the alternator voltage is more
than this set point.
Charging Alternator
Fail Delay
5 to 60 s 10 s
If the alternator voltage is more than the set
point for high voltage when
User manual 4189341340A EN Page 35 of 76