5.3.5 Setup indicators with 360° scales
Set zero position
The sensor/input must be positioned at desired zero value and on the indicator, the set-up switch must be closed:
After 5 seconds, the indicator pointer will move to 0 degree (just check, no action).
Between 5 and 10 seconds, the new zero scale value is stored when set-up switch is opened (the LED will flash once for
verification).
NOTE When controlled by a processor, a switch close time of 5.5 to 9.5 sec must be used.
If no new value was stored (switch still closed), wait until
 seconds. Then the calibration sequence will be terminated
without storing a new setting and the indicator pointer will move back to the scale position given by the present sensor/
input value (normal mode).
Set CCW rotation
On the indicator, the set-up switch must be closed:
After 5 seconds, the indicator pointer will move to scale zero (just check, no action)
After 10 seconds, the pointer will present input values as CCW
After 15 seconds, it will move to minimum scale value (check, no action)
Between 10 and 15 seconds, CCW rotation value is stored when set-up switch is opened (the LED will flash once for
verification)
NOTE
When controlled by a processor, a switch close time of 10.5 to14.5 seconds must be used.
If no new value was stored (switch still closed), wait until  seconds. Then the calibration sequence will be terminated
without storing a new setting and the indicator pointer will move back to the scale position given by the present sensor/
input value (normal mode).
Set CW rotation
On the indicator, the set-up switch must be closed:
After 5 seconds, the indicator pointer will move to scale zero (just check, no action)
After 10 seconds, the pointer will present input values as CCW
After 15 seconds, the pointer will present input values as CW
Between 15 an 20 seconds, CW rotation value is stored when set-up switch is opened (the LED will flash once for
verification)
NOTE
When controlled by a processor, a switch close time of 15.5 to 19.5 seconds must be used.
If no new value was stored (switch still closed), wait until  seconds. Then the calibration sequence will be terminated
without storing a new setting and the indicator pointer will move back to the scale position given by the present sensor/
input value (normal mode).
5.4
Commissioning Single and Dual CANopen indicators
After power-up the LED is flashing once every second, and after two seconds the LED is turned off.
If the LED keeps flashing, there is no communication over both CANopen lines. If the microprocessor stops, the heartbeat
signal on the CAN bus is interrupted and the error LED keeps flashing.
The default setup of the CANopen is Baud rate 125 kbit/s, alternatively the Baud rate can be changed to 250 kbit/s. For
further information regarding the CAN communication, please see the CAN specification manual at www.deif.com.
Installation and commissioning guide 4189350024O EN
Page 31 of 39

Table of Contents

Other manuals for Deif XL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif XL and is the answer not in the manual?

Deif XL Specifications

General IconGeneral
BrandDeif
ModelXL
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals