DLS / DLS-C Series
107
Cod.: 240.010.0042
ALARM TYPE SOLUTION
E028 Battery not recognized. Check the connections and polarity at the BATTERY inputs.
Check the battery voltage and make sure it is within the limits allo-
wed for operation.
Refer to the section "Electrical connections".
If the problem persists, contact the technical support service.
E029 Circuit breaker tripped. Check the correct positioning of the inverter and that the installa-
tion complies with the provisions contained in this manual in the
"Position-ing" and "Mounting" sections.
Check that the ambient temperature is within the allowed range.
Check the correct operation of the cooling fans.
Check that there is no accumulation of dust near the ventilation ope-
nings.
If the problem persists, contact the technical support service.
E030 Overload protection
(EPS & SMART ISLAND
operating mode)
Check the sizing and the output connections to the system.
Reduce the domestic and/or privileged loads connected to the in-
verter.
Refer to the section "Electrical connections".
If the problem persists, contact the technical assistance service.
E031 Wrong AC connection. Check the sizing and the output connections to the system.
Refer to the section "Electrical connections".
If the problem persists, contact the technical assistance service.
E032 Communication fault with
the external energy meter.
Check the communication cable and connection with the energy
meter. Check the energy meter conguration and system settings.
Switch off and restart the system.
Refer to the sections "System switching off" and "System switching
on"
Should the problem persist, contact our technical support service.
E033 Converter control system
fault.
Switch off and restart the system.
Refer to the sections "System switching off" and "System switching
on"
Should the problem persist, contact our technical support service.
E034 Converter control system
fault.
Switch off and restart the system.
Refer to the sections "System switching off" and "System switching
on"
Should the problem persist, contact our technical support service.
E035 Converter control system
fault.
Switch off and restart the system.
Refer to the sections "System switching off" and "System switching
on"
Should the problem persist, contact our technical support service.
E036 Battery temperature out of
range (only LEAD AC-ID).
Check the presence and connections of the battery temperature
sen-sor (lead-acid battery).
Check the battery voltage and make sure it is within the limits allo-
wed for operation.
Check that the ambient temperature is within the allowed range.
Check the correct positioning of the battery and that the installation
complies with the requirements contained in this manual.
Refer to the section "Electrical connections".
If the problem persists, contact the technical support service.
E037 Converter control system
fault.
Switch off and restart the system.
Refer to the sections "System switching off" and "System switching
on"
Should the problem persist, contact our technical support service.