110
Cod.: 240.010.0042
DLS / DLS-C Series
DLS 300 DLS 450 / DLS 450H DLS 600L / DLS 600
AC output
Grid connection 1P+N+PE
Sn nominal power 3 kVA 4.5 kVA 6 kVA
P maximum active power 3 kW 4.5 kW 6 kW
AC voltage range 230 Vac ± 15% (*)
Output nominal current 13 A 19.6 A 26.1 A
Grid nominal frequency 50 Hz
Frequency range 47 Hz - 53 Hz (*)
Cos ϕ 1 (adj ± 0.80)
THD < 3 %
EPS output
Maximum Smax power (PV+BATT) 3 kVA 4.5 kVA 6 kVA
Maximum Smax power (BATT) 3 kVA 3 kVA / 4.5 kVA 3 kVA / 4.5 kVA
AC voltage range 230 Vac ± 15% (*)
Output nominal current 13 A 19.6 A 26.1 A
Grid nominal frequency 50 Hz
Intervention time < 5 sec (*)
THD < 3%
Operating performance
Maximum Effciency 97 %
Weighted effciency (Euro) 96 %
Battery typical effciency 94 %
Protective devices
DC polarity reversal As standard
BATTERY polarity reversal As standard
BATTERY overload protection As standard
AC short-circuit protection As standard
Isolation monitoring unit As standard
Interface protection and anti-islanding In compliance with local legislation
RCMU (Residual Current Monitoring Unit) As standard
DC Overvoltage protective device As standard
AC Overvoltage protective device As standard
BATTERY Overvoltage protection As standard
Accessories supplied
DC connectors Quick connectors
AC connectors Screw terminals, M25 cable gland
BATTERY connection Screw terminals, M25 cable gland
DC switch As standard
BATTERY automatic switch Built-in
User Interface Graphic Touch Screen 4.3’’ colour LCD
Communication interfaces USB / CAN Bus / RS485 / Ethernet / Wi-Fi
External alarm signal As standard
Datalogger Built-in