DLS / DLS-C Series
79
Cod.: 240.010.0042
PARAMETER VALUE DESCRIPTION
PV Meter Setup
No meter Internal energy meter enabled (Default)
ET112 Carlo Gavazzi ET112 external energy meter enabled
ET340 Carlo Gavazzi ET340 external energy meter enabled
EM210 Carlo Gavazzi EM210 external energy meter enabled
10. "AC HYBRID" - The page allows to enable / disable the HYBRID AC operating mode.
PARAMETER VALUE DESCRIPTION
AC HYBRID ON/OFF HYBRID AC operation enable (Default = OFF)
11. "3-PHASE CONF." - The page allows to enable / disable the single-phase compensation operation
mode over a three-phase network relying on a three-phase external energy meter.
PARAMETER VALUE DESCRIPTION
3-Phase Conf. ON/OFF 1 phase compensation over 3 phase network enable (Default = OFF)
12. "BACKUP RESERVE" - The page allows to enable / disable the RESERVE BACKUP mode and set
the SOC reserve level to be used in EPS mode.
PARAMETER VALUE DESCRIPTION
Backup Reserve Sel. ON/OFF BACKUP RESERVE operation enable (Default = OFF)
SOC Backup Reserve 0 - 100% Reserve level SOC
13. "SMART ISLAND SETUP" - The page allows to enable / disable the SMART ISLAND operating mode
and set the SOC levels to enable and disable the battery charge from external motor generator.
PARAMETER VALUE DESCRIPTION
Smart Island Sel. ON/OFF SMART ISLAND operation enable (Default = OFF)
SOC Start ch. 0 – 100% SOC level to enable battery charge from external motor generator
SOC Stop ch. 0 – 100% SOC level to disable battery charge from external motor generator
14. "FEED-IN CONTROL" - The page allows to enable / disable the FEED-IN CONTROL mode to limit
the injection of the energy produced into the network and to set the limit value.
PARAMETER VALUE DESCRIPTION
Feed-in Sel. ON/OFF FEED-IN CONTROL operation enable (Default = OFF)
P Limit 0 – 100'000 W Limit of the power fed into the grid (DEFAULT = 0)
15. "N PE" - The page allows to enable / disable the automatic connection of the NEUTRAL line to the
EARTH potential during the inverter's off-grid operation (EPS and SMART ISLAND operating modes).
PARAMETER VALUE DESCRIPTION
N PE
ON/OFF
Automatic connection of the NEUTRAL line to PE enable during EPS and
SMART ISLAND operating mode (Default = ON)