DLS / DLS-C Series
83
Cod.: 240.010.0042
- "TIMER LD" Function
t
P start
P start–Physt
PV / P
grid
power
Contact ON
Contact OFF
delay
Hysteresis gap (P hyst)
The TIMER LD function allows you to set a smart load contact deactivation delay.
The function is useful to prevent sudden and repeated activations/deactivations of the contact that
could damage the loads subjected to it (e.g. heat pump, air conditioner).
- -"START TIME & STOP TIME" Function
t
Contact ON
START TIME & STOP TIME operation frame
P start
P start–Physt
START TIME
STOP TIME
PV / P
grid
power
The START TIME & STOP TIME time function allows you to set a time frame to activate the SMART LOAD
contact.
Events that exceed the set thresholds outside the set time frame are ignored by the system.
2. "BATTERY MANAGER" - The page allows to set the BATTERY MANAGER operating mode. The
settings are accessible only in the INSTALLER mode which require a password to be logged in (see
the "LOGIN menu" section).
PARAMETER VALUE DESCRIPTION
Battery Manager Sel. ON/OFF BATTERY MANAGER operation enable (Default = OFF)
Batt. Disch. - Start Time hh:mm Battery discharge start time
Batt. Disch. - Stop Time hh:mm Battery discharge stop time
Batt. Ch. - Start Time hh:mm Battery charge start time