Table 20. Supported video resolution options
Resolution Refresh rate (Hz) Color depth (bits)
1024 x 768 60 8, 16, 32
1280 x 800 60 8, 16, 32
1280 x 1024 60 8, 16, 32
1360 x 768 60 8, 16, 32
1440 x 900 60 8, 16, 32
1600 x 900 60 8, 16, 32
1600 x 1200 60 8, 16, 32
1680 x 1050 60 8, 16, 32
1920 x 1080 60 8, 16, 32
1920 x 1200 60 8, 16, 32
Environmental specifications
NOTE: For additional information about environmental certifications, refer to the Product Environmental Datasheet located
with the Documentation on www.dell.com/support/home.
Table 21. Continuous Operation Specifications for ASHRAE A2
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
1035°C (5095°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C (10.4°F) minimum dew point to 80% RH with 21°C
(69.8°F) maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 m (1.8°F/984 Ft) above 900
m (2953 Ft)
Table 22. Continuous Operation Specifications for ASHRAE A3
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
540°C (41104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C (10.4°F) minimum dew point to 85% RH with 24°C
(75.2°F) maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (1.8°F/574 Ft) above 900
m (2953 Ft)
Table 23. Continuous Operation Specifications for ASHRAE A4
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
545°C (41113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C (10.4°F) minimum dew point to 90% RH with 24°C
(75.2°F) maximum dew point