General Tab
Page 24 of 84 eZFC-424R4-24 Application Guide
Edition 2.6
Global Settings
The following fields are found in the Global Settings section.
Field Name Description
Application
Type
Select the main HVAC system application for this controller. This determines
the algorithm that will be used for the controller.
The options for the eZFC-424R4-24 and eZ-440R4-230 controllers are
FanCoil_ (Fan Coil Unit), HeatPump_ (Heat Pump), RadiantHeat_ (Radiant
Heat) and None.
The configurable controller has no functional state until you select an
algorithm.
In a fully programmable controller, when you select an algorithm, you can
override portions of the internal algorithm to suit your needs. See the section
in this guide about overwriting the algorithm. Select None if you want to
program a fully custom sequence of operations. When you select None, the
internal algorithms are disabled and all preconfigured algorithm I/O points and
variables are removed from the default database. Other object types, like AIC,
that were part of the algorithm can be used as is or reconfigured.
If you change an application type for another, the settings of the
previous application type will be deleted. You can save your
controller database before switching application types.
Temperature
Units
Displays the temperature units used by the controller.
Child
Controller
(enteliWEB
only)
If this controller reports to a parent controller, select this box. The child
controller polls these variables from its parent controller:
l HeatCoolLoad (AV802)
l OccupancyMode (MV800)
l DemandCtrlVent (AV813)
l ManualFanSpeedCmd (AV17)
l FanMode (BV1)
When FanMode is set to Automatic in the parent controller, the child
controller’s fan speed is controlled automatically based on demand. When
FanMode is set to Manual, the child controller’s fan speed follows the
ManualFanSpeedCmd value polled from the parent. In this mode, local fan
speed switch or stat fan control button will be suppressed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Controls eZFC-424R4-24 and is the answer not in the manual?

Delta Controls eZFC-424R4-24 Specifications

General IconGeneral
BrandDelta Controls
ModeleZFC-424R4-24
CategoryController
LanguageEnglish

Related product manuals