Local Inputs Tab
Page 32 of 84 eZFC-424R4-24 Application Guide
Edition 2.6
setpoint slider. In the SetpointSliderMaxResistance field, enter the maximum resistance
of the setpoint slider.
To enter the occupancy setpoint offset range for this resistive slider, go to the Setpoints tab
and enter the ± offset in the OccSetpointOffsetRange field.
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
For a list of input configuration software objects that correspond to each function, see the Input
Configuration Objects topic.
Setting Up Damper Feedback
This topic describes how to set up damper position feedback using the Local Inputs tab on the
configuration page. The actuator must have a position feedback feature.
Set Up Damper Feedback
1. Wire the actuator to the controller's physical input.
2. Next to the input number that you've assigned to the actuator, in the Function field, select
Damper1Feedback_.
If a tristate output is assigned to a damper, the algorithm will use this feedback signal rather
than a calculated damper position based on runtime.
3. In the Action/Scale Range field, select the input scale range that matches your damper
feedback signal. If you do not select a scale range, the default scale range is assumed to be
zero to full scale 0 to 100%.
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.