Setpoints Tab
Page 52 of 84 eZFC-424R4-24 Application Guide
Edition 2.6
When a zero value is entered in this field, there is no offset and you will not be able to enter a
setpoint offset on the LINKnet tab nor will a user will able to adjust the setpoint at a stat interface.
Eco Mode Setback (EcoModeSetBack)
The setback amount when the network sensor is in Eco mode.
For example, when you enter a value of 1.0, the setback is -1.0 from the heating setpoint and +1.0
from the cooling setpoint.
Standby Setback (StandbySetback)
The setback amount when the network sensor is in Standby occupancy mode.
For example, when you enter a value of 1.0, the setback is -1.0 from the heating setpoint and +1.0
from the cooling setpoint.
Discharge Air Temperature Limiting Setpoint Differentials
These setpoint fields are only enabled if you had configured a discharge air temperature sensor on
the Local Inputs tab.
Discharge Air Temperature High Limit Setpoint Differential (DATHiLimitSetpointDiff)
Discharge Air Temperature High Limit Setpoint Differential. Used to calculate the maximum limit
above the CurrentHeatSetPoint (AV800) maintained by the enteliZONE algorithm during ducted
heating stages.
Discharge Air Temperature Low Limit Setpoint Differential (DATLowLimitSetpointDiff)
Discharge Air Temperature Low Limit Setpoint Differential. Used to calculate the minimum limit
below the CurrentCoolSetpoint (AV801) maintained by the enteliZONE algorithm during ducted
cooling stages.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Controls eZFC-424R4-24 and is the answer not in the manual?

Delta Controls eZFC-424R4-24 Specifications

General IconGeneral
BrandDelta Controls
ModeleZFC-424R4-24
CategoryController
LanguageEnglish

Related product manuals