LINKnet I/O Tab
Page 50 of 84 eZFC-424R4-24 Application Guide
Edition 2.6
Function
Recommended
corresponding
DNS-24L button
Select this option if you want to:
TempDown_ Button 3
Decrease the temperature setpoint by 0.5
degrees with each buttonpress. The 0.5 degree
amount cannot be changed in the enteliZONE
configurable controller model. In the
programmable controller model, this setting can
be overridden using GCL.
In the additional settings, in the
OccSetpointOffsetReset field, you can turn on
the Occupancy Setpoint Offset Reset function*.
TempUp_ Button 4
Increase the temperature setpoint by 0.5
degrees with each buttonpress. The 0.5 degree
amount cannot be changed in the enteliZONE
configurable controller model. In the
programmable controller model, this setting can
be overridden using GCL.
In the additional settings, in the
OccSetpointOffsetReset field, you can turn on
the Occupancy Setpoint Offset Reset function*.
TempSelect_ Not applicable Recommended for use with the eZNS network
sensor.
FanDown_ Button 3 (DNS
Fan model)
Decrease the displayed fan speed or toggle
through fan stages after FanCycle is pressed.
With analog fans, fan speed will change by this
amount = (FanMaxSpeed FanMinSpeed) / 4.
FanUp_ Button 4 (DNS
Fan model)
Increase the displayed fan speed or toggle
through fan stages after FanCycle is pressed.
With analog fans, fan speed will change by this
amount = (FanMaxSpeed FanMinSpeed) / 4.
FanCycle_ Not applicable
Recommended for use with the eZNS network
sensor.
FanSelect_ Not applicable
Recommended for use with the eZNS network
sensor.
* Occupancy Setpoint Offset Range resets the occupancy setpoint offset at the start of a new
occupancy period.