enteliZONE Database Configuration Objects
Page 78 of 84 eZFC-424R4-24 Application Guide
Edition 2.6
Object Name
Object
Ref
Default Description
HeatCool
ChangeoverDelay
AV104 5
minutes
Time delay between heating and cooling to
prevent overshoot when the heating and
cooling setpoints are close together. Range
between 1 to 30 minutes.
Standby Setback AV105 1
Celsius
Extra setpoint offset added in standby mode.
EcoMode Setback AV106 1
Celsius
Amount of setback that gets subtracted from
heating and added the cooling setpoints when
controller is in eco mode.
OccSetpoint Off-
setRange
AV107 3
Celsius
Determines the offset range available to
change the Occupied Heating and Cooling
setpoints at a LINKnet stat interface or a
hardwired setpoint adjust input.
OATHeat Lock-
outSetpoint
AV160 99
Celsius
Outside air temperature heat lockout setpoint.
DATHiLimit Set-
pointDiff
AV161 25
Celsius
Discharge air temperature high limit setpoint
differential.
HeatingDemandLimit AV163 100% Heating demand limit.
OATCool Lock-
outSetpoint
AV165 -99
Celsius
Outside air temperature cooling lockout
setpoint. Not used by VAV/VVT systems.
DATLowLimit Set-
pointDiff
AV166 15
Celsius
Discharge air temperature low limit setpoint.
CoolingDemand
Limit
AV167 100% Cooling demand limit.
CO2OccOnSetpoint AV182 900
ppm
CO2 high limit occupancy setpoint.
CO2OccOffSetpoint AV183 700
ppm
CO2 low limit occupancy setpoint.
CO2Demand
VentSetpoint
AV185 1100
ppm
CO2 demand ventilation setpoint.