Chapter 4 Parameters
VFD-EL-W 
4-60 
 
Group 5: Multi-Step Speed Parameters 
 You can set this parameter during operation. 
05.00 
1st Step Speed Frequency   Unit: 0.01
05.01 
2nd Step Speed Frequency  Unit: 0.01
05.02 
3rd Step Speed Frequency   Unit: 0.01
05.03 
4th Step Speed Frequency   Unit: 0.01
05.04 
5th Step Speed Frequency   Unit: 0.01
05.05 
6th Step Speed Frequency   Unit: 0.01
05.06 
7th Step Speed Frequency   Unit: 0.01
  Settings  0.00–400.00Hz   Default: 0.00
  The multi-function input terminals (refer to Pr.04.06–Pr.04.08) select one of the AC motor drive multi-step 
speeds (maximum of seven speeds). The speeds (frequencies) are determined by Pr.05.00–Pr.05.06 as 
shown in the following table.  
 
 
 
Parameter 
Multi-step speed 
command 1 
Multi-step speed 
command 2 
Multi-step speed 
command 3 
Master 
frequency 
Master speed 
OFF  OFF  OFF 
1
st
 speed  05.00  ON  OFF  OFF 
2
nd
 speed  05.01  OFF  ON  OFF 
3
rd
 speed  05.02  ON  ON  OFF 
4
th
 speed  05.03  OFF  OFF  ON 
5
th
 speed  05.04  ON  OFF  ON 
6
th
 speed  05.05  OFF  ON  ON 
7
th
 speed  05.06  ON  ON  ON