Chapter 1 Introduction 
 VFD-EL-W 
1-8     
 
Minimum Mounting Clearance 
          (Blue arrow) 
Inflow 
 (Red arrow) Outflow        (Black) Distance  
Single Drive Installation
Side-by-Side Horizontal Installation  Zero-stack Installation 
 
 
Model Name 
Installation 
Method 
Minimum Distance (mm) 
Temperature °C 
A  B  C 
Note 1
Max.(Derating is not 
required)
 Note 3
 
Max.(Derating is 
required) 
VFD002EL21W(-1)
Single Drive  120  50  -  50  60 
VFD004EL21W(-1)
Side-by-Side 
Horizontal 
120  50  30  50  60 
VFD004EL43W(-1)
Zero-stack
 Note 2
-  -  -  -  - 
VFD007EL21W(-1)
Single Drive  120  50  -  50
 Note 4
  60 
Side-by-Side 
Horizontal 
120  50  30  50
 Note 4
  60 
Zero-stack
 Note 2
-  -  -  -  - 
VFD007EL43W(-1)
VFD015EL43W(-1)
Single Drive  120  50  -  50  60 
Side-by-Side 
Horizontal 
120  50  30  50  60 
Zero-stack  -  -  -  -  - 
VFD015EL21W(-1)
VFD022EL21W(-1)
VFD022EL43W(-1)
VFD040EL43W(-1)
Single Drive  150  50  -  50  60 
Side-by-Side 
Horizontal 
150  50  30  50  60 
Zero-stack  150  50  0  40  50