Chapter 4 Parameters
VFD-EL-W 
4-90 
 
 
 
 
 
  When the PID function is enabled and the sleep mode is disabled: 
  If Pr.01.08 > Pr.01.05, the lower limit of the AC motor drive output frequency H is limited by Pr.01.08. 
  If Pr.01.08 ≤ Pr.01.05, the lower limit of the AC motor drive output frequency H is limited by Pr.01.05. 
When it reaches Pr.01.05, the AC motor drive stops output and is in ready status. 
 
10.17 
PID Offset 
      Default: 0.00
  Settings:  0.00–60.00 Hz 
  Selects the minimum output frequency in the PID control mode according to your applications.  
 
10.18 
Feedback of PID Physical Quantity Value  Unit: 0.1
  Settings  1.0–99.9  Default: 99.9
  When you set Pr.00.04 to 8, 00:00 displays (see the figure below). 
  Use this parameter only for display. This parameter does not relate to Pr.00.13, Pr.00.14, Pr.02.18 and 
Pr.02.19. 
 
 
10.19 
PID Calculation Mode Selection 
      Default: 0
  Settings  0  Serial mode 
    1  Parallel mode 
  Serial mode 