Chapter 4 Parameters
VFD-EL-W 
4-54 
 
  Mode 1 
(Pr.04.19=0) 
0: MI1 Start-up (keypad FWD lights) / Stop 
  Mode 2 
(Pr.04.19=1) 
0: Two-wire (1) MI1, MI2 
1: Two-wire (2) MI1, MI2 
2: Three-wire, MI1, MI2, MI3 
  Pr.04.19 determines the setting range and function for Pr.04.04. 
  Mode 1 (Pr.04.19=0): MI1 controls the start-up / stop, and MI2 / MI3 / MI4 are set as multi-function terminals. 
  Mode 2 (Pr.04.19=1): two-wire (1)/two-wire (2) MI1 and MI2 are used for start-up/stop and forward/reverse 
control; MI3 and MI4 are set as multi-function terminals; three-wire (MI1, MI2 and MI3) are used for start-
up/stop and forward/reverse control; MI4 is set as the multi-fucntion terminal. 
  There are four different control modes: 
Setting for Pr.04.19
Setting for Pr.04.04  External terminal control circuit 
Mode 1 
Pr.04.19=0 
Pr.04.04=0 
Single-wire 
FWD/STOP 
Mode 2 
Pr.04.19=1 
Pr.04.04=0 
Two-wire (1) 
FWD/STOP, 
REV/STOP 
Pr.04.04=1 
Two-wire (2) 
RUN/STOP, 
REV/FWD 
Pr.04.04=2 
Three-wire  
Operation Control 
 
04.05 
Reserved 
04.06 
Start-up/Stop or Multi-function Input Terminal (MI2)  
 
  Default: 1
04.07 
Start-up/Stop or Multi-function Input Terminal (MI3) 
 
  Default: 2
04.08 
Multi-function Input Terminal (MI4)  
 
  Default: 3
 
Settings  0–28 
 
Settings
Function  Description 
0  No Function 
Program any unused terminals to 0 to ensure they have no effect 
on operations. 
1  Multi-Step Speed Command 1
Use these three terminals to set the seven-step speed operation. 
There are nine steep speed frequencies (including Master 
Frequency and Jog Frequency) available. 
2  Multi-Step Speed Command 2
3  Multi-Step Speed Command 3
4  Reserved