Chapter 4 Parameters
VFD-EL-W 
4-46 
 
Settings
Function  Description 
24 
Preheating Function 
Indication 
Active when the preheating function is enabled. 
25  Fire Mode Indication 
Active when MI is set to 27 or 28 (fire mode).  
※  “Active” means ON or low voltage. 
 
03.01 
Reserved 
 
03.02 
Desired Frequency Reached  Unit: 0.01
  Settings  0.00–400.0 Hz   Default: 0.00
  If you set a multi-function output terminal to function as Desired Frequency Reached (Pr.03.00–Pr.03.01 = 09), 
then the output is activated when the output frequency reaches the Pr.03.02 setting. 
-2Hz
4Hz
ON
ON
ON
ON
ON
ON
range
master
frequency
desired
frequency
03.02
detection 
range
during stop
Time
waiting time
for 
frequency
run/stop
(output signal)
desired freq. attained
setting 03 zero speed indication
setting 19 zero speed indication
                             output timing chart of multiple function terminals 
 when setting to frequency attained or zero speed indication
 
 
03.03 
Reserved 
 
03.04 
Reserved 
 
03.05 
Terminal Count Value   Unit: 1
  Settings  0–9999  Default: 0
  Sets the count value of the internal counter.  
You can use the external multi-function input terminals on the control terminals to trigger the counter. When 
the count reaches the setting value, the specified output terminal activates by setting one of the multi-function 
input terminals (the count value resets after reaching the setting for Pr.03.05). 
 
When the display shows c555, the drive has counted 555 times. If the display shows c555, it means that the 
actual counter value is between 5,550 and 5,559. 
 
03.06 
Preliminary Count Value  Unit: 1
  Settings  0–9999  Default: 0
  When the counter value counts from c1 to this setting value, the corresponding multi-function output terminal 
activates. You can use it as an indication for the AC motor drive running at low speed to stop when the 
counting is going to reach the setting value before stop. 
  The timing diagram shows as follows: