Chapter 2 Installation and Wiring
 VFD-EL-W 
2-4 
 
Wiring for NPN and PNP mode 
Internal power supply 
External power supply 
 
1.  Separate the main circuit and control circuit wiring to prevent erroneous actions. 
2.  Use shielded wire for the control wiring and do not expose the peeled-off shield in front of the terminal. 
3.  Use shielded wire or conduit for the power wiring and ground the two ends of the shielded wire or conduit. 
4.  Damaged insulation of wiring may cause personal injury or damage to circuits and equipment if it comes in 
contact with high voltage. 
5.  The AC motor drive, motor and wiring may cause interference. To prevent equipment damage, take care of 
interference between the surrounding sensors and the equipment. 
6.  Connect the AC drive output terminals U/T1, V/T2, and W/T3 to the motor terminals U/T1, V/T2, and W/T3, 
respectively. To permanently reverse the direction of motor rotation, switch over any of the two motor leads. 
7.  With long motor cables, high capacitive switching current peaks can cause over-current, high leakage current 
or lower current readout accuracy. To prevent this, the motor cable should be less than 20 m for 4.0 kW 
models and below. The cable should  be  less  than 50 m for 5.5 kW models and above. For longer motor 
cables, use an AC output reactor. 
8.  The  AC  motor  drives,  electric  welding  machines  and  the  larger  horsepower  motors  should  be  grounded 
separately. 
9.  Use ground leads that comply with local regulations and keep them as short as possible. 
10.  The VFD-EL-W series does not have a built-in brake unit,and no support for external brake unit and brake 
resistor. 
11.  When grounding, choose wires that comply with local regulations for your safety. 
12.  To prevent lightning strike and electric shock, the metal grounding wire of electrical equipment should be 
thick and short, and connected to the dedicated grounding terminal of the inverter system. 
13.  You  can  install  multiple  VFD-EL-W  units  in  one  location.  All  the  units  should  be  grounded  directly  to  a 
common ground terminal, as shown in the figure below. Ensure that there are no ground loops.