Chapter 4 Parameters
VFD-EL-W 
4-52 
 
Example 8:  
This example uses negative slope. With these settings, the AC motor drive always runs in only one direction 
(reverse). 
 
   
 
04.11 
Minimum AVI Voltage 
 
  Unit: 0.1
 
  Default: 0.0
 
Settings  0.0–10.0 V 
04.12 
Minimum AVI Frequency (percentage of Pr.01.00) 
 
  Unit: 0.1
 
  Default: 0.0
 
Settings  0.0–100.0 % [100% corresponds to Fmax (Pr.01.00)] 
04.13 
Maximum AVI Voltage 
 
  Unit: 0.1
 
  Default: 10.0
 
Settings  0.0–10.0 V 
04.14 
Maximum AVI Frequency (percentage of Pr.01.00) 
 
  Unit: 0.1
 
  Default: 100.00
 
Settings  0.00–100.00% [100% corresponds to Fmax (Pr.01.00)] 
04.15 
Minimum ACI Current 
 
  Unit: 0.1
 
  Default: 4.0
 
Settings  0.0–20.0 mA 
04.16 
Minimum ACI Frequency (percentage of Pr.01.00) 
 
  Unit: 0.1
 
  Default: 0.0
 
Settings  0.00–100.00% [100% corresponds to Fmax (Pr.01.00)] 
04.17 
Maximum ACI Current 
 
  Unit: 0.1
 
  Default: 20.0
 
Settings  0.0–20.0 mA 
04.18 
Maximum ACI Frequency (percentage of Pr.01.00) 
 
  Unit: 0.1
 
  Default: 100.0
  Settings  0.00–100.00% [100% corresponds to Fmax (Pr.01.00)] 
  These parameters set the analog input reference values. The minimum and maximum frequencies are set 
based on Pr.01.00 (during open-loop control) as shown in the following diagrams.