Chapter 4 Parameters
VFD-EL-W 
4-71 
 
  Settings  0.1–5.0 sec.  Default: 0.5
  When the AC motor drive detects a momentary power loss, it blocks its output and then waits for a period of 
time specified by this parameter before resuming operation. Set this parameter at a value that ensures that 
any residual regeneration voltage from the motor on the output has disappeared before the drive is activated 
again. 
  This parameter also determines the waiting time before resuming operation after an External Base Block and 
Number of Auto-restarts after Fault (Pr.08.15). 
 
08.08  Current Limit for Speed Search  Unit: 1
  Settings  30–200%  Default: 150
  Limits the drive output current during a speed search. 
  When executing a speed search, the V/F curve is defined by the settings in Parameter Group 01. 
 
 
08.09 
Skip Frequency 1 Upper Limit  Unit: 0.01
08.10 
Skip Frequency 1 Lower Limit  Unit: 0.01
08.11 
Skip Frequency 2 Upper Limit  Unit: 0.01
08.12 
Skip Frequency 2 Lower Limit  Unit: 0.01
08.13 
Skip Frequency 3 Upper Limit  Unit: 0.01
08.14 
Skip Frequency 3 Lower Limit  Unit: 0.01
  Settings  0.00–400.00 Hz  Default: 0.00
  These parameters cause the AC motor drive not to remain in these frequency ranges with continuous 
frequency output. Set these six parameters as follows Pr.08.09  Pr.08.10  Pr.08.11  Pr.08.12  Pr.08.13  
Pr.08.14. 
0
08.09
08.10
08.11
08.12
08.13
08.14
 
 
08.15 
Number of Auto-restarts After Fault  Unit: 1
  Settings  0–10  Default: 0
08.16 
Auto-reset Time for Restart after Fault  Unit: 0.1
  Settings  0.1–6000 sec.  Default: 60.0
  After an over-current OC or over-voltage OV fault occurs, the AC motor drive can automatically reset/restart 
up to ten times. 
  Setting this parameter to 0 disables automatic reset/restart operation after any fault. 
When enabled, the AC motor drive restarts with speed search, which starts at the last frequency before the 
fault.