Chapter 6 Fault Code Information and Maintenance 
 VFD-EL-W 
6-6 
 
6.2 Maintenance and Inspections 
Before the check-up, always turn off the AC input power for at least five minutes and remove the 
cover. Even if the power has been turned off, a charge may still remain in the filter capacitors with 
hazardous voltages before the power is OFF. Make sure the voltage is lower than 25 V
DC
 before 
you perform any inspections.
 
 
Ambient environment 
Items to Check  Methods and Criterion 
Maintenance Period 
Daily  Half Year  One Year 
Check the ambient 
temperature, humidity, 
vibration and for any dust, gas, 
oil or water drops. 
Visual inspection and 
measurement with equipment 
with standard specifications 
   
Check for any dangerous 
objects in the environment. 
Visual inspection     
 
Voltage 
Items to Check  Methods and Criterion 
Maintenance Period 
Daily  Half Year  One Year 
Check if the voltages of 
the main circuit and 
control circuit are correct. 
Measure with multi-meter with 
standard specifications. 
   
 
Digital keypad display 
Items to Check  Methods and Criterion 
Maintenance Period 
Daily  Half Year  One Year 
Check that the display is 
clear for reading. 
Visual inspection     
Check for any missing 
characters in the display. 
Visual inspection     
 
Mechanical parts 
Items to Check  Methods and Criterion 
Maintenance Period 
Daily  Half Year  One Year 
Check for any abnormal 
sounds or vibrations. 
Visual and auditory inspection     
Check for any loose 
screws. 
Tighten the screws     
Check for deformed or 
damaged parts. 
Visual inspection     
Check for any color 
change due to 
overheating. 
Visual inspection       
Check for any dust or dirt.  Visual inspection