Chapter 4 Parameters
VFD-EL-W 
4-17 
 
Group 8 Special Parameters 
Parameter
Explanation  Settings  Default
Customer
08.00  DC Brake Current Level
0–100%  0   
08.01 
DC Brake Time during 
Start-Up 
0.0–60.0 sec.  0.0 
 
08.02 
DC Brake Time during 
Stopping 
0.0–60.0 sec.  0.0 
 
08.03  Start-point for DC Brake 
0.00–400.0 Hz  0.00   
08.04 
Momentary Power Loss 
Action  
0: Operation stops (coast to stop) after  
momentary power loss 
0 
 
1: Operation continues after momentary power 
loss, speed search starts with the last 
frequency 
2: Operation continues after momentary power 
loss, speed search starts with the minimum 
frequency 
08.05 
Maximum Allowable 
Power Loss Time 
0.1–20.0 sec.  2.0 
 
08.06 
Base Block Speed 
Search 
0: Disable 
1: Speed search starts with the last frequency  
command 
2: Speed search starts with the minimum output  
Frequency (Pr.01.05) 
1 
 
 
08.07 
Base Block Time for 
Speed Search (B.B.) 
0.1–5.0 sec.  0.5 
 
08.08 
Current Limit for Speed 
Search 
30–200%  150 
 
08.09
Skip Frequency 1 Upper 
Limit  
0.00–400.00 Hz   0.00 
 
08.10
Skip Frequency 1 Lower 
Limit  
0.00–400.00 Hz  0.00 
 
08.11
Skip Frequency 2 Upper 
Limit  
0.00–400.00 Hz  0.00 
 
08.12
Skip Frequency 2 Lower 
Limit  
0.00–400.00 Hz  0.00 
 
08.13
Skip Frequency 3 Upper 
Limit  
0.00–400.00 Hz  0.00 
 
08.14
Skip Frequency 3 Lower 
Limit 
0.00–400.00 Hz  0.00 
 
08.15 
Number of Auto-restarts 
after Fault 
0–10  0 
 
08.16 
Auto-reset Time for 
Restart after Fault 
0.1–6000 sec.  60.0 
 
08.17  Auto-energy Saving 
0: Disable Energy-saving operation 
0 
 
1: Enable Energy-saving operation 
08.18 
Automatic Voltage 
Regulation (AVR) 
0: AVR function enable 
0 
 
1: AVR function disable 
2: AVR function disable for deceleration 
3: AVR function disable for stop 
08.20
Compensation 
Coefficient for Motor 
Instability 
0.0–5.0  0.0 
 
08.21 
DC Current Level during 
Preheating 
0–100%  0 
 
08.22 
DC Current Cycle Time 
during Preheating 
0–100%  0 
 
08.23  Fire mode 
0:No function 
1:Forward running 
2:Reverse in reverse 
0 
 
08.24 
Operating Frequency 
during Fire Mode 
0.00–400.00 Hz  60.00