Chapter 4 Parameters
VFD-EL-W 
4-103 
 
For multi-pump operating at constant pressure (Pr.10.35=2 Fixed Quantity Control) 
Related parameters when setting Pr.10.35=2  
Parameter
Function  Settings  Default
End 
master
End 
slave
Note 
00.03
Start-
Selection 
0: Display the frequency 
command value (F) 
0  3  3 
 
1: Display the actual output 
frequency (H) 
 
2: Display the output current 
in Amps supplied to the 
motor (A) 
 
3: Display the content of 
user-defined unit (U) 
 
4: FWD/REV command   
00.04
Content of 
Multi-function 
Display 
0: Display the content of the 
user-defined unit (U) 
0  8  8 
 
1: Display the counter value 
(c) 
 
2: Display the status of 
multi-function input 
terminals (d) 
 
3: Display the DC bus 
voltage (u) 
 
4: Display the output voltage 
(E) 
 
5: Display the PID analog 
feedback signal value in 
% (b) 
 
6: Display the output power 
factor angle (n) 
 
7: Display the output power 
(P) 
 
8: Display the setting values 
for PID control and 
feedback signal 
 
9: Display the AVI (I) (V)   
10: Display the ACI (mA/V) 
(i) 
 
11: Display the temperature 
of the IGBT in °C (h) 
 
00.13 
User-defined 
Value  
(corresponds to 
max. operating 
frequency 
Pr.01.00) 
0–9999  0  100  100 
Sets the constant pressure 
control to correspond to the 
largest physical quantity and 
the decimal place. The 
number displayed is 10.0 
currently. 
00.14 
Decimal Place 
of User-defined 
Value  
0–3  0  1  1