Chapter 4 Parameters
VFD-EL-W 
4-106 
 
Parameter
Function  Settings  Default
End 
user’s 
master
End 
user’s 
slave
Note 
10.23
Detection 
Time of Set 
Point 
Deviation 
Level 
1–9999 sec.  10  10  10 
decelerate to stop. This 
deceleration time is 
according to the 
Deceleration Time 2 in 
Pr.01.12. When the feedback 
value is < 2.85 kg, the AC 
motor drive starts to run. 
10.24
Deviation 
Level of Liquid 
Leakage 
0–50%  0  33  33 
Liquid Leakage: 
Assume that when the AC 
motor drive does not run and 
is in a constant pressure 
status, the variation of the 
feedback value is less than 
0.12 kg (3 kg X 4% = 0.12 
kg) within 2 seconds. When 
the feedback value continues 
to decrease to make the 
deviation of the set point be 
less than 0.99 kg (3 kg X 
33% = 0.99 kg), that is, when 
the feedback value is less 
than 2.01 kg, the AC motor 
drive starts to run. 
Liquid Usage after Liquid 
Leakage: 
Assume that when the AC 
motor drive does not run and 
is in a constant pressure 
status, the variation of the 
feedback value is higher 
than 0.12 kg (3 kg X 4% = 
0.12 kg) within 2 seconds, 
the AC motor drive starts to 
run. 
10.25
Liquid 
Leakage 
Change 
Detection 
0–100%  
(0: Disable) 
0  4  4 
10.26
Time Setting 
for Liquid 
Leakage 
Change 
0.1–10.0 sec. 
(0: Disable) 
0.5  2  2 
10.35 
Multi-pump 
Control Mode 
0: Disable 
1: Fixed time circulation 
(alternativeoperation) 
2: Fixed quantity control (multi-
pump operating at constant 
pressure) 
0  2  2 
 
10.36  Multi-pump ID
0: Multi-pump control mode is 
disabled 
1: Master 
2–4: Slave 
0  1  2 
 
10.37
Multi-pump’s 
Fixed Time 
Circulation 
Period 
1–65535 minutes  60  1  1 
 
10.42
Pump’s 
Frequency at 
Time-out 
(Disconnection)
0.00 Hz–FMAX  0.00  60  60