Chapter 6 Fault Code Information and Maintenance 
 VFD-EL-W 
6-4 
 
Fault Name  Fault Descriptions  Corrective Actions 
 
Communication Fault 
1.  Check the RJ45 connection between the AC motor 
drive for loose wires and wiring to the correct pins. 
2.  Check if the communication protocol is properly set. 
3.  Refer to Parameter Group 09 Communication 
Parameters in Chapter 4 for detailed information. 
 
PID feedback signal fault 
1.  Check the parameter settings (Pr.10.01) and AVI/ACI 
wiring. 
2.  Check for possible fault between the system response 
time and the PID feedback signal detection time 
(Pr.10.08) 
 
Software protection failure  Password locked. 
 
Analog signal error  Check if the wiring for ACI is broken. 
 
Unusual PID feedback 
Check if wiring for PID feedback is correct and the 
parameter of PID feedback is properly set. 
 
Phase Loss  Check if the input power is three-phase. 
 
Multi-motor fault protection 
Check if the motor wiring is normal.