Chapter 4 Parameters
VFD-EL-W 
4-7 
 
Parameter
Function  Setting  Default
Customer
02.08 
Accel./ Decel. Rate of Change 
of UP/DOWN Operation with 
Constant Speed 
0.01–10.00 Hz / 2ms  0.01 
 
02.09
Second Frequency Command 
Source 
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. 
1: 0–10V from AVI  
2: 4–20 mA from ACI 
3: RS-485 (RJ45) communication 
4: Digital keypad potentiometer 
0 
 
02.10
Combining the First and 
Second Master Frequency 
Commands 
0: First Master Frequency Command Only 
1: First Master Frequency Command+ Second 
Master Frequency Command 
2: First Master Frequency Command - 
Second Master Frequency Command 
0 
 
02.11
Keypad Frequency Command
0.00–400.0 Hz  60.00
 
02.12
Communication Frequency 
Command 
0.00–400.0 Hz  60.00
 
02.13 
Saving Keypad or 
Communication Frequency 
Command Selection 
0: Save Keypad & Communication Frequency
0 
 
1: Save Keypad Frequency Only 
2: Save Communication Frequency Only 
02.14 
Initial Frequency Selection 
keypad & RS-485) 
0: Current Frequency Command 
0 
 
1: Zero Frequency Command 
2: Refer to Pr.02.15 to set up 
02.15 
Initial Frequency Setting (for 
keypad & RS-485) 
0.00–400.0 Hz  60.00
 
02.16 
Display the Master Frequency 
Command Source 
Read Only 
1: bit0=1: First Master Frequency Source  
(Pr.02.00) 
2: bit1=1: Second Master Frequency Source 
(Pr.02.09) 
4: bit2=1: Multi-function input 
Read
only 
 
02.17 
Display the Operation 
Command Source 
Read Only 
1: bit0=1: Digital Keypad 
2: bit1=1: RS-485 communication 
4: bit2=1: External Terminal (MI1) 
8: bit3=1: Multi-function input 
Read
only 
 
02.18  User-defined Value 2 Setting  0–Pr.00.13  0   
02.19  User-defined Value 2  0–9999 
Read
only