OPERATOR’S MANUAL
PM200, 200E and 250 Planter Monitors
11001-1444-200702
ALARMS / 37
ALARMS
NOTE: An audible 2-chirp alarm is also
output during navigation or data
entry to indicate an illegal or
nonfunctional key selection.
Primary operating alarms are displayed on the entire screen and are
accompanied by an audible alarm.
HOPPER LEVEL
Hopper level alarms activate when the seed level drops below the sensor
mounting level (Figure 28). Alarm can be silenced by pressing the Alarm
Cancel key.
Figure 28
Hopper 1 And 2 Alarms
ROW FAILURE
A row failure alarm occurs when the console detects less than 2 seeds per
second through the seed tube. This may also result from a poor or faulty
connection to the seed sensor harness. This is a solid-on alarm, as shown
in (Figure 29), indicating a problem has been detected and is silenced by
pressing the Alarm Cancel key.
Once the Alarm Cancel key is pressed, the alarm will not sound again
unless:
1. Planting condition returns to a normal state and falls again below 2
seeds per second.
2. Power on/off sequence occurs before problem is corrected.
3. An All Rows Failure alarm occurs and then the console again detects
less than 2 seeds per second through the seed tube.