E-13
English
Configuring the Heat Pump Heating System 6.1
   
  
°C
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
return temperature, which is the product of the
maximum calculated flow temperature minus
the temperature difference in the heating
system (spread).
20 °C
... 30 °C ...
70 °C
Heating circuit 1
Regulation according
to external
temperature
 
  
Sets the desired return set temperature when
fixed-setpoint regulation is selected
15 °C
... 40 °C ...
60 °C
Heating circuit 1
Heating circuit 1
fixed-setpoint
  
  
Sets the desired room set temperature and I
ratio when room temperature regulation is
selected
15.0 °C / 001
... 20.0 °C .../ ...60 ...
30.0 °C / 999
Heating circuit 1
Heating circuit 1
reference room
  
 
Sets the minimum return temperature when
room temperature regulation is selected
15 °C
... 20 °C ...
30 °C
Heating circuit 1
Heating circuit 1
reference room
  
 
Different maximum temperatures are
permissible for panel and radiator heating
systems. The upper limit of the return set
temperature can be set between 25 °C and
70 °C.
25 °C
... 50 °C ...
70 °C
Heating circuit 1
 
  
The return set temperature hysteresis forms
the neutral zone for operation of the heat pump.
If the temperature “Return set temperature plus
hysteresis” is reached, the heat pump switches
itself off. If the temperature “Return set
temperature minus hysteresis” is reached, the
heat pump switches itself on.
0.5 K
... 2 K ...
5 K
Heating circuit 1
  

Settings to lower the heating characteristic
curve of heating circuit 1
Heating circuit 1
 


Sets the time during which the temperature in
heating circuit 1 is to be lowered
00:00
...
23:59
Heating circuit 1
 
 
Sets the temperature value by which the
heating characteristic curve of heating circuit 1
is to be lowered when the temperature is
lowered
0 K
...
19 K
Heating circuit 1
 
  
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is
lowered. Operations to lower the temperature
that exceed a week day are activated or
deactivated at the end of each day accordingly.
N
T1
T2
Y
Heating circuit 1
  

Settings to raise the heating characteristic
curve of heating circuit 1
Heating circuit 1
 


Sets the time during which the temperature in
heating circuit 1 is to be raised.
00:00
...
23:59
Heating circuit 1
 
 
Sets the temperature value by which the
heating characteristic curve of heating circuit 1
is to be raised.
0 K
...
19 K
Heating circuit 1
 
  
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is raised.
Operations to raise the temperature that
exceed a week day are activated or deactivated
at the end of each day accordingly.
N
T1
T2
Y
Heating circuit 1

System-specific parameters
Setting range Display