34 XR Fire Control Panel User Guide | Digital Monitoring Products, Inc.
TEMP CODE
When you select YES for this menu
option, and this profile is assigned to
a user code (see next section), the
keypad displays TEMP EXPIRE DATE.
Enter the ending date for the profile to
expire. Default is seven days from today.
The system deletes Temp users at 12:00
AM on the last date.
ANTI PASS NO
Anti-passback requires that you
properly exit (egress) an area
previously accessed. When you fail to
exit through the proper location you
cannot access it until you properly exit.
Default is NO.
ACCESS SCHEDULES
This option allows you to assign
two Schedules to a profile for door
access. When the keypad displays
FIRSTACCESSSCHEDULE press
COMMAND to browse available
Schedules. Enter the Schedule
number and press COMMAND.
When the keypad displays
SECONDACCESSSCHEDULE repeat
the same process for the third through
eighth access schedule and press
COMMAND to return to the User Menu.
RE ARM DELAY
This option allows the entry of 0 to 720
minutes to be used to delay automatic
rearming when the user disarms an
area outside of schedule. If zero is
selected, the rearming occurs based on
permanent programming in the panel.