W2940305 Rev 07 8/2019 Dover Fueling Solutions 27
4.2.4.2 Set the Date and Time
Change Time & Date
Step IRC Command
Sale $
Display
Volume
Display
Unit
Price
Display
4 Go to time & date function Type<2> & Press <ENTER>
- - - - - - [blank] F 02
5 Go to time sub-function Press <ENTER> again
- - - - - -
[time in HH.MM
format]
(if time is correct
skip to step 8)
2.00
6 Clear display Press <#>
[blank]
[time in HH.MM
format]
2.00
7 Enter current time
Type the current time in the 24-
hour format of HHMM & Press
<ENTER>
- - - - - -
[entered time in
HH.MM format]
2.00
8 Go to month/day sub-
function
Press <NEXT>
- - - - - -
[date in MM.DD
format] (if date is
correct skip to
step 11)
2.01
9 Clear display Press <#>
[blank]
date in MM.DD
format
2.01
10 Enter current month/day
Type the current date in the
format of MMDD & Press
<ENTER>
- - - - - -
[entered date in
MM.DD format]
2.01
11 Go to year sub-function Press <NEXT>
- - - - - -
[Year in YYYY
format] (if the year
is correct skip to
step14)
2.02
12 Clear display Press <#>
[blank]
Year in YYYY
format
2.02
13 Enter current year
Type the current year in the
format of YYYY & Press
<ENTER>
- - - - - -
[entered year in
YYYY format]
2.02
14 Return to function level Press <ENTER> again
- - - - - - [blank] F 02
4.2.4.3 Set the Correct Filling Mode of Operation
Dispensers are shipped configured for standalone/pulse output operation. If this is the mode
you plan to use for this dispenser, skip to step 20.
Set Filling Mode of Operation (Standalone or Serial Interface)
Step IRC Command
Sale $
Display
Volume
Display
Unit
Price
Display
15 Go to Set Filling Mode of
Operation
Type<1> & Press <ENTER>
- - - - - - [blank] F 01
16 Go to Filling Mode sub-
function
Press <ENTER> again
- - - - - -
[Filling Mode in X
format, 1=Serial
Mode,
2=Standalone
mode]
1.00
17 Clear display Press <#>
[blank]
[Filling Mode in X
format, 1=Serial
Mode,
2=Standalone
mode]
1.00
18 Enter desired Filling Mode
Enter the desired Filling Mode,
1=Serial Mode
2=Standalone/ Pulse Output
Mode & Press <ENTER>
- - - - - -
[Filling Mode in X
format, 1=Serial
Mode,
2=Standalone
mode]
1.00
19 Return to function level Press <ENTER> again
- - - - - - [blank] F 01