67 of 105
The GSC400 will display a message and sound the buzzer for a set amount of tim
Alarm Delay) to alert nearby personnel that the generator is about to start. The
engine/generator will run for a set period of time (Run Duration) and then shut down.
e (Pre-
he Start Date and Start Hour determine the date (0 to 31) and time when the
ngine/generator will first start. After the first exerciser start, the engine/generator will
en by the Repeat Freq which is measured in hours.
T
e
start up on regular intervals giv
The exerciser feature depends on the GSC400 internal clock. Make sure the clock is set
to the proper time and date.
GSC400 internal clock inform ain “in memory” for approximately 2 weeks ation can rem
when no DC power is suppli e ed to the controller. Two week memory storage is availabl
in a completely charged cont lly roller clock. DC power is required to be supplied continua
to the GSC400 for approximately 1 hour to allow for a completely charged clock.
The remote start contacts (RSC) are ignored in an exerciser started run until the
GSC400 enters cool-down or AUTO. To prevent the engine from shutting down set the
cool-down time to a value ot the GSC400 will detect the her than 0. While in cool-down
RSC and will go back into the RUN mode without shutting down.
6.8 Digital Input Setup
There are eight digital inputs. Each input can be selected to any of the features given in
Table 15 below.
Table 15 – Digital Input Selections
Name Description
Low Air Pressure This input generates a Low Air Pressure failure when active only
in Crank. It is ignored in the OFF, AUTO, and RUN modes.
Low Hydraulic Pressure This input generates a Low Hydraulic Pressure failure when
active only in Crank. It is ignored in the OFF, AUTO, and RUN