6.14 Set Dummy Load
The dummy load feature allows the user to turn on an output if the AC current is below a
settable threshold (Load On Point). This is useful for applications where the generator
must have a minimal load to prevent damage to the generator.
Upon crank success (RUN Mode entered), if enabled, the feature waits for a configurable
bypass time, then starts to monitor the AC current. If the AC current remains below the
Load On Point for 6.5 seconds then the dummy load digital output is turned on. If the
AC current rises and remains above a settable threshold (Load Off Point) for 1.5s, the
dummy load digital output is turned off.
A digital output must be set to dummy load to use this feature.