9.3 CT’s (Current Transformers)
Current transformers are required for display of AC current. One CT is required for each phase to
be displayed. The wiring for CT’s is as follows:
In single phase applications:
Figure 12 – AC current sensing
connections.
• Phase A to terminals Phase A*
• Phase B to terminals Phase B*
In three phase applications:
• Phase A to terminals Phase A*
• Phase B to terminals Phase B*
• Phase C to terminals Phase C*
In center tap delta applications:
• Phase A to terminals Phase A*
• Phase B to terminals Phase B*
• Phase C to terminals Phase C*
* White wire assumed positive. Black wire assumed
negative.
Table 21 – Current Transformers Part List
CT Description Stock Code Manufacturer’s Part No.
100A:5A ACC0045 PC&S-546-100-L
200A:5A ACC0046 PC&S-546-200-L
300A:5A ACC0047 PC&S-546-300-L
500A:5A ACC0048 PC&S-546-500-L
600A:5A ACC0049 PC&S-546-600-L
1000A:5A ACC0050 PC&S-546-1000-L
1500A:5A ACC0057 PC&S-546-1500-L