Criterion Tested in accordance with Values
Ambient mechanical conditions
Protection mode IP20
Vibrations: IEC 60068-2-6 5 ... 9 Hz (constant
amplitude 3.5 mm)
9 ... 150 Hz (constant
acceleration 1 g)
Shock IEC 60068-2-27 18 shocks
(half-sine wave
15g/11 ms)
Drop IEC 60068-2-31 Drop height 50 mm
Free fall (packaged) IEC 60068-2-32 1 m
Electro-magnetic compatibility (EMC)
Emission(Conducted
Emission)
EN 55022 Class B
Emission(Radiated
Emission)
EN 55022 Class B
Harmonics(Current
Harmonics)
EN 61000-3-2
Flicker(Voltage
Fluctuation)
EN 61000-3-3
ESD(Electrostatic
Discharge)
EN 61000-4-2
Severity 3
8 kV air discharge
6 kV contact
discharge
RF-Field(Radiated
Immunity)
EN 61000-4-3 3V/m
Burst(Electrical Fast
Transients)
EN 61 000-4-4 1 kV (supply and
sig nal lines)
Surge(Transients
comm.&diff.mode)
(applies only to
ELC-AC types)
EN 51000-4-5 0.5kV
RF-com.mode(RF
continues conducted)
EN 61000-4-6
V-dips(Voltage dips
and Interruption)
EN 61000-4-11
Cycle time
Cycle time per
function
<0.01ms