9.2 UPS system input
Rated input voltage 220/380 V; 230/400 V; 240/415 V
Voltage tolerance (Rectifier input) 230 V -20% / +20%
Voltage tolerance (Bypass input) 230 V -15% / +10%
Rated input frequency 50 or 60 Hz, user configurable
Frequency tolerance 40 to 72 Hz
Number of input phases (rectifier & bypass) 3 phases, + N
Input power factor 0.99
Rated/maximum mains input current
See Tables
9
and
11
Input current distortion at rated input cur-
rent, iTHD
30 kW: < 4,5%
40–200 kW, 60 kVA: < 3%
Rectifier ramp-up, rectifier start and load
step
10 A/s (default), configurable.
Min 1 A/s
Backfeed protection Yes, for rectifier and bypass lines
9.3 UPS system output
Table 23: Eaton 93PM 30–200 kW UPS system output
Number of output phases
3 phases + N
Rated output voltage 220/380 V; 230/400 V;
240/415 V; configurable
Rated output frequency 50 or 60 Hz, user
configurable
Total voltage harmonic distortion:
100 % linear load
100 % non-linear load
< 1%
< 3%
Rated output frequency 50 Hz or 60 Hz, configurable
Output frequency variation ±0.1 Hz
Slew rate 0.4 Hz/s
Output current See Table
8
and Table
10
Overload capability at
ambient 40 °C
(on inverter)
10 min 102–110% load
60 s 111–125% load
10 s 126–150% load
300 ms > 150% load
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 112 (126)