Figure 46. Maintenance bypass mode
A Static bypass input 1 Maintenance Bypass Switch (MBS)
B Rectifier input
C Out
7.8 Turning the UPS from the maintenance bypass mode
to the double conversion mode
To turn the UPS back to the double conversion mode:
1. Follow the normal start position:
Figure 47. Maintenance bypass mode
A Static bypass input 1 Maintenance Bypass Switch (MBS)
B Rectifier input
C Out
2. Turn on the rectifier switch to connect rectifier input to the UPS.
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 105 (126)