CAUTION
To reduce the risk of a fire, connect only to a circuit that is provided with
maximum input circuit breaker current ratings from Table
10
and Table
11
in
accordance with the national and local installation rules.
The line-to-line unbalanced output capability of the UPS is limited only by the full
load per phase current values for AC output to critical load shown in Tables
10
and
11
. The recommended line-to-line load unbalance is 50% or less.
Source protection for the AC input to bypass must suit the characteristics of the
load and take into account effects such as inrush or starting current.
Bypass and output overcurrent protection and bypass and output disconnect
switches must be provided by the user.
4.4 Unpacking and unloading the UPS
Before you start to unpack and unload the UPS, examine the TipNTell indicator
on the package surface and the DropNTell indicator on the UPS after unpacking
(see step 2 below). If the equipment has been correctly transported in the
upright position, the indicator should be intact. If the indicator arrow has turned
all blue, contact the appropriate parties to report inappropriate transportation.
WARNING
The UPS cabinet is heavy. If you do not obey the unpacking instructions, the
cabinet can tip over and cause serious injury.
Do not tilt the UPS cabinet more than 10 degrees from the vertical or the
cabinet can tip over.
For transportation purposes, the UPS cabinet is bolted onto a wooden pallet. To
remove the pallet:
1. Before you unload the cabinet
from the pallet, use a forklift or
other material handling
equipment to move the cabinet
to the installation area. Insert
the forks of the forklift between
the skids on the bottom of the
unit.