Ambient operating temperature range, 60
kVA model
From +5 °C ... +30 °C
Relative humidity range 5 to 95%, no condensation allowed
Maximum service altitude
1,000 m (3,300 ft) above sea level at +40
°C
Maximum 2,000 m (6,600 ft) with 1% derat-
ing per each additional 100 m above 1,000
m.
Maximum storage time with internal batter-
ies
6 months without discharge
*Maximum recommended operating and storage temperature for UPS with internal bat-
teries is +25 °C. Higher storage temperature will shorten the maximum storage time
without recharging.
9.5 Battery specification
Battery type VRLA, 12 VDC
Recharge profile Advanced Battery Management (ABM) or
float charge
End of discharge voltage 1.67 VPC to 1.75 VPC, configurable or au-
tomatic (load adaptive)
Battery start option Yes
Charging current capability Configurable, 0 to 29.3 A / UPM
At > 40 kVA / UPM load, automatically limi-
ted to maximum 16.5 / UPM
93 PM UPS kVA 30, 40, 50 or 60 kVA
with internal battery
30, 40, 60, 80, 120
or 160 kVA, no inter-
nal battery
50, 100, 150 or 200
kVA, no internal bat-
tery
Battery quantity, per
battery string
36 blocks,
216 cells
32 to 40 blocks,
192 to 240 cells
36 to 40 blocks,
216 to 240 cells
Battery voltage
range
432 V (36 blocks) 384 V (32 blocks) to
480 V (40 blocks)
432 V (36 blocks) to
480 V (40 blocks)
Note:
Do not connect battery strings with different battery quantity and voltage in
parallel!
Eaton 93PM UPS 30–200 kVA User's and installation guide
©