Temperature rise of max. +5 °C requires the airflow of 600 m
3
/h per 1 kW of
losses
Temperature rise of max. +10 °C requires the airflow of 300 m
3
/h per 1 kW
of losses
An ambient temperature from +20 to +25 °C is recommended to achieve a long
life of the UPS and batteries. The cooling air entering the UPS must not exceed
+40 °C. Avoid high ambient temperature, moisture, and humidity.
For ventilation requirements, see 93PM heat rejection in the following table:
Table 7: Air conditioning or ventilation requirements during full load operation
Rating Heat rejection
(BTU/h x 1,000)
Heat rejection
[kW]
30 kW 4.30 1.3
40 kW 5.73 1.7
50 kW 7.16 2.1
54 kW, 60 kVA 7.75 2.3
80 kW 11.45 3.4
100 kW 14.32 4.2
120 kW 17.18 5.0
150 kW 21.48 6.3
160 kW 22.91 6.7
200 kW 28.64 8.4
4.3.2 UPS system power wiring preparations
Note: If you are installing a maintenance bypass, provide one of the following:
- a minimum of 2 separate feeds with upstream feeder breakers or
- a single feed with 2 upstream feeder breakers: one for the UPS or rectifier
input breaker (if installed) and one for the maintenance bypass input.
Do not use a single feed or a single feeder breaker to supply both
- the UPS or rectifier input breaker and
- the maintenance bypass.
If a bypass input breaker is installed in the maintenance bypass and a single-
feed UPS is being installed, a single feed to the maintenance bypass is
acceptable for supplying both the UPS and the bypass.
When you plan and perform the installation, read and understand the following
notes:
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 41 (126)