Figure 10. 93PM air outlets
The clearances required around the UPS cabinet in both of these situations are
shown in Table
6
.
Table 6: UPS cabinet clearances
30–50 kW,
60 kVA
[mm]
80–100 kW
[mm]
120–200 kW
[mm]
80–200 kW
with top air exhaust
kit
[mm]
From the top of the
cabinet
500 500 500 500
From the front of the
cabinet
900 900 900 900
From the back of the
cabinet
200* 200* 300* 0
From the side of the
cabinet
0 0 0 0*
* Cabling may require more space.
The basic environmental requirements for operation of the UPS system are:
• Ambient Temperature Range: from +5 to +40 °C
• Ambient Temperature Range for the 60 kVA UPS cabinet: from +5 to +30 °C
• Recommended Operating Range for VRLA batteries: from +20 to +25 °C
• Maximum Relative Humidity: 95%, noncondensing
It is required to arrange ventilation of the UPS room. Sufficient amount of air
cooling is needed to keep the maximum room temperature rise at desired level:
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 40 (126)