higher signaling circuit voltage requirements, please use Industrial Relay
Adapter in MiniSlot.
5.6.1 Installing customer input signals interface
These inputs are located behind the UPS door, in the top section of the UPS.
See Figure
29
for the connector locations.
Tie points with strain relief for the communication cables are located on the right
and left side of the cable conduit.
Signal inputs can be configured to different functions. Normally these functions
are either informative (for example, “On Generator”) or functional (for example, a
remote “Go to bypass” command).
5.6.2 Battery breaker wiring interface
When using the original accessory battery cabinet from the manufacturer, the
battery breaker interface wiring is provided with the cabinet. The wiring is
connected to the X5 and X6 terminal in the UPS.
When using a third-party battery system, the breaker must be equipped with
auxiliary signal and should have a 24 V shunt trip for remote opening of the
breaker, when needed.
See Section
5.4.2
for installation instructions.
5.6.3 Relay output interface connections
The general alarm relay is a dry relay signal output. The relay can be used for
informing the operators about UPS alarm conditions, for example through a
building management system. By default, the relay is configured to activate
when the UPS general alarm is active, that is, any event when the
ALARM
status is active. The relay can also be configured to activate by some other
event, but this needs to be done by authorized service personnel.
Relay signal wiring can be installed only through the signal cabling canal, from
back to front, in the top section of the UPS.
Additional relay outputs are available with mini-slot cards. Relay outputs can be
configured to be activated by various events. Configuration can be done by an
authorized Eaton Customer Service Engineer or by other qualified service
personnel authorized by Eaton.
5.6.4 Industrial Relay Card interface connections
Relays K1 through K5 are identical in function. Each output contact function can
be assigned by the user. The UPS information may also be configurable.
To install the INDRELAY-MS:
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 71 (126)