Overload capability
at ambient 40 °C
(in the stored energy mode)
10 min 102–110% load
60 s 111–125% load
300 ms > 126% load
Overload capability
at ambient 40 °C
(in the bypass mode)
Continuous ≤ 125% load
10 ms 1,000% load
Note! Bypass fuses may limit the overload
capability.
Load power factor (rated) Nominal 1.0
Load power factor (permitted range) From 0.8 lagging to 0.8 leading
Table 24: Eaton 93PM 60 kVA / 54 kW UPS system output deviations
Overload capability at
ambient 30 °C
(on inverter)
10 min 102–110% load
60 s 111–125% load
60 s 126–150% load
300 ms > 150% load
Overload capability
at ambient 30 °C
(in the stored energy mode)
Continuous < 103% load
60 s 103–105% load
300 ms > 105% load
Overload capability
at ambient 30 °C
(in the bypass mode)
Continuous ≤ 125% load
60 s 103–105% load
Note! Bypass fuses may limit the overload
capability.
Load power factor (rated) Nominal 0.9
Load power factor (permitted range) From 0.8 lagging to 0.8 leading
9.4 UPS environmental specifications
Acoustic noise at 1 m
30–50 kW and 60 kVA: < 60 dBA
80–200 kW: < 65 dBA
ESS operation: < 45 dBA
Ambient UPS storage temperature range From -25 °C ... +55 °C in the protective
package
Internal battery:
+20 °C ... +25 °C in the protective package
Ambient operating temperature range, 30–
200kW models
From +5 °C ... +40 °C*
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 113 (126)