Figure 22. Separate battery option battery terminals for 93PM 200 kW
1
Battery + for UPM 1 5 Battery - for UPM 1
2 Battery + for UPM 2 6 Battery - for UPM 2
3 Battery + for UPM 3 7 Battery - for UPM 3
4 Battery + for UPM 4 8 Battery - for UPM 4
Table 15: Recommended battery cable and fuse sizes for separate battery
Separate battery per UPM
Battery cable, Pos. & Neg. line [mm
2
] 1 x 50
Battery fuse [A] 200
Table 16: Rated and maximum battery currents for rated power
Rated current [A] Maximum current [A]
Separate battery per UPM 122 146
5.4.2 Battery trip wiring
The 50 kW UPS units are always equipped with an internal battery breaker. The
100–150 kW units can be with or without an internal breaker. The 200 kW unit
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 65 (126)